Heat loss estimator
A quick estimate of a house heat loss in BTU/h from the local design temperature and envelope quality, with a furnace size and heat pump tonnage. An estimate, not a CSA F280 calculation.
Your job
Regional estimating design temperature. Verify the applicable current design data for the project jurisdiction.
Answer
- Design heat loss
- 24,422 BTU/h (7.2 kW)
- Furnace
- 60,000 BTU/h input (57,600 output)
- Heat pump
- 2 tons of heating; nearest 2 ton
- Design temperature
- -18 °C outdoors, 22 °C indoors (40 °C difference)
- Walls and windows
- 6,011 walls, 7,308 windows and doors
- Ceiling and foundation
- 1,620 ceiling, 2,951 foundation
- Air leakage
- 6,532 BTU/h at 0.35 air changes per hour
- The smallest furnace is more than 140% of the load; the house may short-cycle. Consider a modulating unit.
- This is a rough estimate from typical assemblies, not a CSA F280 heat loss calculation. A permit or a final equipment selection needs F280.
- Design temperature -18 °C is an estimating input. Verify the applicable current design temperature for the project jurisdiction before final equipment selection. Indoor design temperature is 22 °C.
Method: Regional design-temperature data used for estimating; verify the applicable current design data for the project jurisdiction before final equipment selection; Method: sum of U x area x temperature difference for walls, ceiling, windows, doors and foundation, plus infiltration at 1.08 x CFM x temperature difference; Estimate only, not CSA F280-12; assembly U-values and air changes are typical by envelope quality
Estimating aid based on a summary of the CEC. Provinces adopt different editions and amendments. Confirm with the authority having jurisdiction, and the engineer of record where one is involved.
Priced takeoff
- High-efficiency gas furnace 60,000 BTU$2,455.311 ea at $2,455.316 h
- Cold-climate ducted heat pump 2 ton$5,372.191 ea at $5,372.198 h
- Materials
- $7,827.50
- Labour, 14 h at $108.00
- $1,512.00
- Your cost, before markup and tax
- $9,339.50
Reference prices are dated baselines (2026-11) for Ontario. Confirm them with your supplier. In TradeQuote PRO your own saved prices replace these.
How it works
You enter 9 inputs. The calculator returns the quantities, rounds them up the way the material is sold, and lists the takeoff so it can be priced.
- City. Regional estimating design temperature. Verify the applicable current design data for the project jurisdiction.
- Heated floor area above grade, all floors (sq ft).
- Storeys.
- Ceiling height (ft).
- Envelope quality.
- Window area (sq ft).
- Exterior doors.
- Foundation.
- Furnace efficiency (AFUE) (%).
The method
- Regional design-temperature data used for estimating; verify the applicable current design data for the project jurisdiction before final equipment selection
- Method: sum of U x area x temperature difference for walls, ceiling, windows, doors and foundation, plus infiltration at 1.08 x CFM x temperature difference
- Estimate only, not CSA F280-12; assembly U-values and air changes are typical by envelope quality
Check results against the code and manufacturer data that apply to your job. Prices are dated baselines to confirm with a supplier.
Add this to a real estimate in TradeQuote PRO
The takeoff lands as estimate lines with your prices, markup and tax, then becomes a proposal the client signs.